Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
Serious damage to
the building’s electrical system may occur
without this transfer switch.
NOTICE
When connecting the generator to a isolation (transfer)
switch, have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the Auto Off/Reset Manual switch is placed
in the mode, the generator will automatically
start in the event of commercial power falling below a
prescribed level by means of a contact closure that is
generated automatically by a transfer switch.
In this position (, should an outage occur, the
automatic transfer switch (ATS) will start the generator
automatically via the generator's auto-start contacts
connected to the ATS's start contacts.
Please refer to your ATS installation manual for further
instructions for the correct installation of the auto-start
contacts of the generator to the ATS
When running the generator in the mode,
remember the generator can start up at any time without
warning. attempt to perform any maintenance
when the generator is in the auto mode.
NOTICE
When the Auto Off/Reset Manual switch is placed
in the position, the engine glow plugs will be
warmed and the engine will start automatically.
When starting generator in mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the (Figure 41)
in the position
Switch (AUTO)
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 7).
NOTICE
The engine speed switch must be set to the “High”
position when running in the mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
GENERATOR START-UP PROCEDURE (AUTO MODE)