
DCA45SSIU4F
To shutdown the generator, use the following procedure:
1. Place both the circuit breakers
as shown in Figure 47 to the OFF position.
Figure 47. Main, Aux. and GFCI
Circuit Breakers (Normal OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the (Figure 48)
in the position.
Figure 48. Switch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
1. To shut-down the engine in the event of an emergency,
switch the , GFCI and (Figure 49) circuit
breakers to OFF position.
Figure 49. Main, Aux. and GFCI
Circuit Breakers (Emergency OFF)
This unit is equipped with safety devices to automatically
stop the engine in the event of low oil pressure, approximately
14 psi (97 kPa), or high water temperature, approximately
212° F (100° C), overspeed approximately +15%. The alarm
lamps on the ECU illuminate to signify the reason for the
shutdown.
NOTICE
Before inspecting generator, check that the Auto/
Manual Switch is in the position, and
place all circuit breakers in the OFF position. Allow
sufficient time for adequate cooling. When ready to
restart, complete all steps in the Generator Startup
Procedure section of this manual.
GENERATOR SHUT-DOWN PROCEDURES
Kommentare zu diesen Handbüchern